Rugged case-style housing with IP40 (open case), IP53 (closed case) for excellent protection from the elements
Electrical safety: IEC 61010-1; 50 V CAT IV; Double insulation
Large, backlit 2 x 16-character alphanumeric display with adjustable contrast provides good visibility in all lighting conditions.
Gear measurement of transformers (VT/PT) and current transformers (CT); Measuring method in accordance with IEEE C57.12.90™-2006
Direct transmission ratio reading from 0.8000 : 1 to 8000.0 : 1 for transformers (VT/PT) and from 0.8000 : 1 to 1000.0 : 1 for current transformers (CT)
Primary-circuit current forcing with secondary-side reading for greater safety
Display of gear ratio, excitation current, winding polarity and % deviation with respect to nameplate parameters
Protection against the creation of dangerous measurement voltages - tests are carried out at low voltage and with reduced excitation current, and protection is provided against accidental interchange of measurement channels H (primary side) and X (secondary side)
Display of messages about wrong wire connection, reversed polarity, open circuit and short circuit
Choice of digital filters for improving indication stability in environments with electrical interference.
Built-in memory with the ability to store up to 10000 measurement results
Communication interface: USB 2.0, optical isolation, transmission speed 115.2 kB
Standard included PC software Data View for configuring the device, analyzing data read from the meter, collecting results, creating reports using standard or custom templates
Power supply: rechargeable NiMH 2x12 V - 1650 mAh batteries (operating time up to 10 hours - battery discharge indicator); Charger with charging time < 4 hours