CHAUVIN ARNOUX C.A 6117 installation tester.



The tester is a specialized, multifunctional instrument designed to test the most important parameters of installations. It is distinguished by simplicity of operation, an easy-to-read display and a large selection of measurement functions.


FEATURES


  • Robust, compact, lightweight housing with IP53 protection class
  • Electrical safety 600 V CAT III, 300 V CAT IV (IEC61557, EC61010 -1)
  • Clear, backlit 5.7" color display with 320 x 240 resolution
  • Easy operation thanks to a rotary switch on the front panel with direct access to all functions
  • Menu in Polish language
  • Help for each function
  • Possibility to save measurement results to memory
  • Measurements in accordance with applicable European standards: IEC6036, EN61557, NF C 15-100, VDE 0100, NIN/NIV, IEE 17th
  • Standard PC software "ICT" allows quick and easy analysis of measurements stored in the tester and its configuration
  • Optional "DataView" software for advanced measurement analysis
  • Power supply: 10.8 V lithium-ion battery with a capacity of 5.8 Ah (approx. 30 h of operation)
  • Dimensions: 280 mm x 190 mm x 128 mm
  • Weight: 2.2 kg


Measurements and tests:


  • Harmonic analysis (calculation of harmonics up to 50th order for current and voltage, calculation of THD coefficients, etc.).
  • Power measurement (0 to 110 kW for one phase and 0 to 330 kW for three phases; displaying values together with voltage and current; measuring power factor)
  • Frequency (from 10 to 500 Hz)
  • Voltage (0 to 550 V AC/DC; DC band and 15.8 to 500 Hz)
  • Current intensity using currentclamps (from 5.0 mA to 199.9 A - current probe C177A; from 5.0 mA to 19.99 A - current probe MN77)
  • Short-circuit loop impedance Zs (between phase and protective conductor)
    • High test current measurement mode up to 5 A (range from 0.1 Ohm to 399.9 Ohm)
    • Small test current measurement mode (installations with a residual current circuit breaker) selectable 6 mA, 9 mA, 12 mA (range from 0.2 Ohm to 3999 Ohm)
    • Short-circuit current calculation (from 0.1 A to 6 kA)
    • Calculation of impedance and its resistive and inductive components

  • Impedance Zi (between two phases or between phase and neutral conductor)
    • High test current measurement mode up to 5 A (range from 0.1 Ohm to 399.9 Ohm)
    • Calculation of impedance and its resistive and inductive components
    • Calculation of short-circuit current (from 0.1 A to 6 kA)
    • Percentage voltage drop across conductors

  • Checking the phase sequence
  • Test of AC and A-type residual current circuit breakers
    • Residual current In: 10, 30, 100, 300, 500, 650, 1000 mA (90 V - 280 V) or 10, 30, 100, 300, 500 mA (280 - 550 V)
    • Three types of measurement modes available: Test in pulse mode (measurement of tripping time; at In, 2 x In, 5 x In ); Test in residual current rise mode (measurement of time and exact value of residual current tripping the differential circuit breaker, rise from 0.3 x In to 1.06 x In in 3.3% In increments ); Test mode without tripping (checking whether the differential circuit breaker will trip at a residual current less than half of the rated In/2 - duration: 1000 ms or 2000 ms)
    • Touch voltage measurement

  • Test of type B residual current circuit breakers
    • Differential current for current build-up and pulse mode 2 x In 10, 30, 100, 300, 500 mA; for pulse mode 4 x In 10, 30, 100 mA
    • Three types of measurement modes available: Test in impulse mode (measurement of tripping time, with 2 x In 4 x In ); Test in differential current rise mode (measurement of time and exact value of differential current triggering the differential circuit breaker, rise from 0.2 x In to 2.2 x In); Test mode without tripping (checking whether the differential circuit breaker will trip at a differential current less than half of the rated In/2 - duration: 300 ms or 600 ms)
    • Touch voltage measurement

  • Measurement of grounding
    • Grounding by 3P method (range: 0.50 Ohm to 15 kOhm)
    • Grounding by 1P method (High current mode up to 5 A - range: 0.10 Ohm to 399.9 Ohm; Measurement mode in a circuit breaker installation with selectable test current: 6 mA, 9 mA, 12 mA - range from 0.20 Ohm to 3999 Ohm)
    • Grounding by 1P selective method (range from 0.50 Ohm to 399.9 Ohm)

  • Continuity measurement of protective, network and equipotential bonding conductors
    • For current I > 200 mA with a range of 39.99 Ohm
      • For current I = 12 mA with a range of 39.99 Ohm and 399.9 Ohm


  • Measurement of insulation resistance of electrical installations
    • Testing voltage 50, 100, 250, 500, 1000 VDC
    • Range from 0.01 MOhm to 2 GOhm