CHAUVIN ARNOUX MN60 current probe
Parameters:
- Bandwidth: 40 Hz - 40 kHz
- Measurement of AC current from 0.1 to 200 A (600 A peak) in two ranges:
Range 1: 0.1 A - 20 A (60 A peak)
Range 2: 0.5 A - 200 A (600 A peak)
- Sensitivity: 100 mV/A (range 1); 10 mV/A (range 2)
- Output signal:
Range 1: 100 mV AC per 1 A AC of measured current (2 V AC for 20 A AC or 6 V peak for 60 A peak)
Range 2: 10 mV AC per 1 A AC of measured current (2 V AC for 200 A AC or 6 V peak for 600 A peak)
- Standard accuracy ≤2% (range 1); ≤1.5% to ≤3.5% (depends on measured current for range 2)
- IP40 rated enclosure
- Electrical safety: 600 V CAT III, 300 V CAT IV (IEC 1010-1 and IEC 1010-2-032)
- Maximum diameter of the measured wire: 20 mm
- Maximum dimension of the measured rail: 20 mm x 5 mm
- Output: 2 m long coaxial cable terminated with an insulated BNC connector
- Dimensions: 135 mm x 57 mm x 34.5 mm
- Weight: approx. 180 g