CHAUVIN ARNOUX Y1N current transformer
Parameters:
- Bandwidth: 48 Hz - 1 kHz
- Current transformer: 1000/1
- Nominal range of AC current measurement: 4 A - 600 A (permissible overload up to 700 A AC for 10 minutes)
- Output signal: 1 mA AC per 1 A AC of measured current (600 mA AC for 600 A AC)
- Standard accuracy of ≤3% to ≤4.5% (depends on the size of the measured current)
- Surge protected output
- IP40 rated enclosure
- Electrical safety: 600 V CAT III, 300 V CAT IV (IEC 1010-1 and IEC 1010-2-032)
- Maximum diameter of the measured wire: 30 mm
- Maximum dimension of the measured rail: 63 mm x 5 mm
- Output: two-wire cable of approx. 1.5 m length terminated with two safe, male "banana" type terminals of 4 mm diameter
- Dimensions: 195 mm x 66 mm x 34 mm
- Weight: approx. 420 g